Fire in a fired heater of an ethylene plant
An explosion of a mixture of hydrogen and hydrocarbons occurred at a fired heater of a refinery. A mixture of a hydrogen and hydrocarbon mixture was accidentally released into the firebox of a fired heater, where it ignited, creating a large fire at a refinery. The fired heater that had been offline for approximately 12 hours due to an unplanned compressor shutdown. During the start-up, after the burners were ignited, the process fluid failed to flow in all four passes. This caused the tube wall temperature to reach 1500 F (815 C), exceeding the design limit. The operator turned out two of the 8 burners and reduced the flow throw the first 3 passes, to help the flow in the forth. An inspection team found the tubes gluing red, but thought to hear the flow in the fourth passes, concluding that the flow meter, which was giving no flow, was malfunctioning, After less than a hour later, a tube in the fourth pass ruptured due to overheating), releasing 1800 kg of a mixture of hydrogen and hydrocarbons into the firebox. The mixture was ignited by the burners producing a large fire. No injuries, estimated that the property damage from the incident was $10 million.

The INITIATING CAUSE was due to lack of flow in one of the fired heater passes, which caused the loss of confinement of one of the tube due to over-heating. The IGNITION was provide by the burners flames CONTRIBUTION and ROOT CAUSES were: (i) the correct start-up procedure was not followed. This procedure required maintaining a steady flow through all four tube-passes before lighting the burners. (ii) the fired heater lacked engineered safeguards to prevent the burners from being lit before establishing flow in each of the four passes.