Fire in a fired heater of an ethylene plant (1169)

This data is from the European Hydrogen Incidents and Accidents database HIAD 2.1, European Commission, Joint Research Centre.

Fire in a fired heater of an ethylene plant

An explosion of a mixture of hydrogen and hydrocarbons occurred at a fired heater of a refinery. A mixture of a hydrogen and hydrocarbon mixture was accidentally released into the firebox of a fired heater, where it ignited, creating a large fire at a refinery. The fired heater that had been offline for approximately 12 hours due to an unplanned compressor shutdown. During the start-up, after the burners were ignited, the process fluid failed to flow in all four passes. This caused the tube wall temperature to reach 1500 F (815 C), exceeding the design limit. The operator turned out two of the 8 burners and reduced the flow throw the first 3 passes, to help the flow in the forth. An inspection team found the tubes gluing red, but thought to hear the flow in the fourth passes, concluding that the flow meter, which was giving no flow, was malfunctioning, After less than a hour later, a tube in the fourth pass ruptured due to overheating), releasing 1800 kg of a mixture of hydrogen and hydrocarbons into the firebox. The mixture was ignited by the burners producing a large fire. No injuries, estimated that the property damage from the incident was $10 million.

Event Date
August 19, 2022
Record Quality Indicator
Classification of the Physical Effects
Nature of the Consequences
Cause Comments

The INITIATING CAUSE was due to lack of flow in one of the fired heater passes, which caused the loss of confinement of one of the tube due to over-heating. The IGNITION was provide by the burners flames CONTRIBUTION and ROOT CAUSES were: (i) the correct start-up procedure was not followed. This procedure required maintaining a steady flow through all four tube-passes before lighting the burners. (ii) the fired heater lacked engineered safeguards to prevent the burners from being lit before establishing flow in each of the four passes.

Facility Information
Application Type
Application
Refinery
Specific Application Supply Chain Stage
Components Involved

heater tube, fire box, fired heater

Storage/Process Medium
Location Type
Operational Condition
Pre-event Summary

The fired heater that had been offline for approximately 12 hours due to an unplanned compressor shutdown.

Consequences
Number of Injured Persons
0
Number of Fatalities
0
Currency
Property Loss (onsite)

10000000

Lessons Learned

An automated safeguard would have prevented the burners from being ignited before the minimum flow was established through each of the four tube passes contributed to the incident. The fact that such a system was not present hint at a lack of realistic accidental scenarios supporting a correct risk assessment.

Event Nature
Release Type
Release Substance
H2, hydrocarbon
Hydrogen Release Concentration (%)
0.00
References
References

CBS incident reports volume 2 https://www. csb. gov/us-chemical-safety-board-releases-volume-2-of-chemical-incident-reports/ accessed April 2025