Skip to main content

Fire in a deposit of metallic waste (1248)

This data is from the European Hydrogen Incidents and Accidents database HIAD 2.1, European Commission, Joint Research Centre.

Fire in a deposit of metallic waste

The event occurred at a centre handling metal waste. A fire broke out in a container for aluminium alloy shavings, while handling it with a grapple excavator. The fire spread throughout the entire building. An operator intervened with a fire extinguisher while the excavator operator, assisted by two others, removed the machine from the building. The 61 employees were evacuated. A plume of dense smoke, visible for several kilometers, rose from the building. Ten residents were confined within the path of the smoke.

Event Date
July 29, 2025
Record Quality Indicator
Event Initiating System
Classification of the Physical Effects
Nature of the Consequences
Cause Comments

The INITIATING CAUSE was the accidental formation of an explosive atmosphere by metallic waste and its ignition during the handling. The waste in question was a historical batch of turnings made of the 7075-aluminium alloy. It had been stored for five years in a humid environment with aged cutting oil. These conditions led to oxidation of the turnings, resulting in a concentrated hydrogen cloud above the container. The IGNTITION SOURCE was probably provided by a spark generated by the collision between one of the grapple's fingers and the container wall The presence of suspended dust may also have contributed to the formation of an explosive atmosphere. The melting of the translucent roof panels may have contributed to the fire spreading within the building. The ROOT CAUSE could be identified in an inadequate risk assessment of the waste storing and handling processes.

Facility Information
Application Type
Application
metallic waste handling
Specific Application Supply Chain Stage
Components Involved

metallic cotnainer, crane

Storage/Process Medium
Storage/Process Quantity
0
Actual Pressure
0
Design Pressure
0
Location Type
Location description

BACKGROUND INFORMATION ON THE ACTIVITIES The company was specialised in recycling of ferrous and non-ferrous materials. On the site effected by the fire, metallic batches were sorted, consolidation and packaged for further processing/recycling. 7075 aluminium alloy (AA7075) is an aluminium alloy with zinc as the primary alloying element and composition: zinc: 6-6. 1% , magnesium: 2. 1-2. 5% , copper: 1. 2-1. 6% [https://en. wikipedia. org/wiki/7075_aluminium_alloy].

Operational Condition
Consequences
Number of Injured Persons
0
Number of Fatalities
0
Currency
Property Loss (onsite)

2400000

Property Loss (offsite)

0

Post-event Summary

Material damage = €2 million Business interruption losses = €400,000.

Lessons Learned

Unwanted hydrogen production from oxidation of metallic waste is a well-documented occurrence. It can come to incidents, due to a combination of factors such as high humidity, long storage periods and, above all, storage in confined spaces, what enable the formation of an explosive hydrogen-air mixture. ARIA source reports that the operator took measures aiming at improving the efficiency of the emergency actions. Nothing is said on possible preventive measures, which could be reduce the probability of formation of the explosive mixture, such as an adequate room ventilation and explosive gas detection.

Event Nature
Emergency Action

The fire was fought by means of water and cement. The smoke triggered a request of home-confinement to few neighbouring houses. EMERGENCY ACTIONS SEQUENCE 9:30 The fire started. At 9:34 - Fire department was called and the shut-off valves were closed. While awaiting the arrival of emergency services, site personnel sprayed the fire with a fire hose reel and a fire hose. 10:00 - The firefighters deployed two fire hoses, one of which was mounted on an aerial ladder. 10:45 - Cement, already on site due to ongoing construction work, was used to smother the fire. A new supply had to be requested from a local provider. 12:45 - The fire was brought under control around. From 12:45 p. m. to 16:00 - The waste was removed from the building and then sprayed with foam to ensure complete extinguishment. Atmospheric readings were taken by emergency services, and the results showed no significant impact. 16:30 - The operation concluded. The firefighting water (approximately 5 m³) was contained on site. It was analysed to determine its discharge point. The waste removed from the building was secured, and the exterior surfaces were cleaned.

Release Type
Release Substance
H2 100% metallic dust
Hydrogen Release Concentration (%)
0.00
Ignition Source
References
References

Event nr 65042 of the French database ARIA https://www. aria. developpement-durable. gouv. fr/accident/65042/ (accessed December 2025)