Failure of a LH2 tank without ignition
During a test of an 8 foot scale tank loaded with LH2, the tank burst at 77 psi (ca. 5. 3 bar) destroying the test installation. No fire or explosion occurred and the area control was successfully recovered within 24 hours. [Ordin, NASA (1974)]
Record Quality Indicator
Event Initiating System
Classification of the Physical Effects
Nature of the Consequences

The IMMEDIATE CAUSE was the rupture of the tank. The test was programmed for 79 psi maximum and the tank burst at 77 psi. The report does not mention it, but a test at 79 psi would suggest that the nominal working pressure (NWP) of the tank was this value or above. Therefore, its Maximum Allowed Working Pressure (MAWP) would have been much higher (it is usually between 2 and 2. 5 ties the NWP). This indicates a failure far below the load capability assumed by design. The ROOT CAUSE was vey probably a manufacturing error. An additional FACTOR contributing to an escalation (the whole testing facility was destroyed) was the lack of an emergency recovery plan for such an emergency.