Skip to main content

Explosion in a waste water tank (69)

This data is from the European Hydrogen Incidents and Accidents database HIAD 2.1, European Commission, Joint Research Centre.

Explosion in a waste water tank

This incident occurred at a waste water tank of an unspecified chemical plant. An explosive atmosphere formed inside the wastewater tank due to the accidental production of hydrogen. This occurred either during wastewater treatment or due to the reaction of excess sodium borohydride from the remaining wastewater in the tank with additional wastewater added to the tank later. The hydrogen-air explosive atmosphere was forced through an overflow pipe and through a water seal and released into the surrounding area, where it was ignited by manual work. Subsequently, a flashback occurred through the overflow pipe into the wastewater tank, resulting in an explosion which destroyed the tank.
Event Date
November 1, 2000
Record Quality Indicator
Region / Country
Event Initiating System
Classification of the Physical Effects
Nature of the Consequences
Cause Comments

The INITIATING CAUSE was an accidental formation of hydrogen by a chemical reaction. The ROOT CAUSE was the lack of effective monitoring and control of the process values, specifically the lack of pH adjustment during filling of the wastewater tank. This hint at shortcoming of the operative procedures, of risk assessment and/or of proper training of operators.

Facility Information
Application Type
Application
waste management
Specific Application Supply Chain Stage
Components Involved
sodium borohydride tank
Storage/Process Medium
Location Type
Operational Condition
Consequences
Number of Injured Persons
13
Number of Fatalities
0
Currency
Property Loss (onsite)

1000000

Post-event Summary

The tank and othe plant componets were destroyed by the explosion and subsequent fire.

Event Nature
Emergency Action
The alarm was triggered manually by a push-button. The area was evacuated, and the combustion products were suppressed by the fire department with a water spray.
Release Type
Release Substance
H2 100%
Hydrogen Release Concentration (%)
0.00
Ignition Source
Detonation
No
Deflagration
No
High Pressure Explosion
No
High Voltage Explosion
No
References
References

Event from German database ZEMA https://www. infosis. uba. de/index. php/de/site/2854/zema/index/3223. html (accessed December 2024)