Explosion at a vent stack
A large quantity of hydrogen was being vented to atmosphere during pre-chill operations. Normal pre-cooling time was about 45 minutes, but due to technical problems, the pre-cooling continued for about 80 minutes. The LH2 tank was pressurised and vented a number of times releasing additional hydrogen. The weather was calm so the hydrogen failed to disperse as quickly as normal. The accumulated gas ignited (unknown source) and the explosion caused damage to the test area. [Ordin, NASA (1974)]
Record Quality Indicator
Event Initiating System
Classification of the Physical Effects
Nature of the Consequences
Causes

The INITATING CAUSE was the unplanned release of large quality of gas at the vent stack, which did not disperse at stack exit but formed an explosive mixture. The large quantity vented was due to a pre-chill procedure which lasted much longer than planned, with consequent need to pressurise the liquid hydrogen tank more times. The ROOT CAUSE could be related to a vent stack design unable to avoid explosions in all cases and/or to mitigate their occurrences (for example venting at the safe distances). An additional factor could be related to operative procedures unable to mitigate the consequences of unplanned events.