Explosion of a potassium storage tank at an ammonia plant
The accident happened in an anhydrous ammonia plant, commissioned in March 1977. Hydrogen accumulated inside a Benfield solution (hot potassium) storage tank and was ignited by a static charge, which caused the explosion. Mechanism by which hydrogen may have entered the storage tank are described in the paper (block valve leakage, H2 solubility in Benfield solution, etc. ). The explosion sent the tank roof and sidewalls some 37m into the air, expelling an estimated amount of 114 m3 of solution into the process area. Major damage was produced on synthesis gas piping in some heat exchangers, instrumentation, air and N2 lines, steam header, electrical equipment, etc. Inspection after the accident revealed greater weld strength at the tank roof to side wall than the floor to side wall welds. This was the cause of sidewalls adhering to the roof and not to the floor during explosion. Neither environmental pollution nor personnel injuries were produced. Many design modifications (different roof type, continuous air purging, better block valve, etc. ) and new operation procedures were implemented.
Event Initiating System
Classification of the Physical Effects
Nature of the Consequences
Cause Comments
INITIATING cause was the injection of hydrogen into the Benfield Solution Storage Tank, with consequent static charge ignition.