Explosion in a metals processing plant due to unexpected hydrogen production (1181)

This data is from the European Hydrogen Incidents and Accidents database HIAD 2.1, European Commission, Joint Research Centre.

Explosion in a metals processing plant due to unexpected hydrogen production

An explosion occurred in the venting system of a metal grinding CNC-unit. The explosion has been attributed to the unexpected reaction between the water used for the cooling of the grinding and the powder produced by the unit, with the production of hydrogen. The powder consisted in aluminium, magnesium and silicium. The local fire brigade intervened (6 vehicles and 27 persons). The clearing of the emergency required to extract the hydrogen-air mixture from the venting system. The fire department deployed an explosion-proof suction device. Nobody was injured.

Event Date
May 13, 2024
Record Quality Indicator
Event Initiating System
Classification of the Physical Effects
Nature of the Consequences
Causes
Cause Comments

The INITATING CAUSE was the unintended hydrogen production from a reaction between metal powder and cooling water. The ROOT CAUSE cannot be identified (yet). It can be assumed that this was a unique case, and that the unit had worked before without this type of incidents. It is unknown if and which modifications to the usual process could have brought to the electrolysis of water in presence of dust.

Facility Information
Application Type
Application
metal grinding
Specific Application Supply Chain Stage
Components Involved

grinding machine

Storage/Process Medium
Actual Pressure
0
Design Pressure
0
Location Type
Operational Condition
Consequences
Number of Injured Persons
0
Number of Fatalities
0
Post-event Summary

Nothing known on the amount of damage. Probably, only the vent duck or system was affected.

Lessons Learned

No specific Lesson Learnt possible, in absence of details on the process, its procedures, the possible changes occurred on the day of the incident and the process parameters. It is known that very fine metal powder, possibly in a dust cloud, is very reactive to explosive oxidation. The assumption made by the fire brigade to explain the explosion is the occurrence of an oxidation reaction between water and the metallic powder, with production of hydrogen which then ignited and exploded. The report, however, does not mention a direct confirmation of presence of hydrogen.

Event Nature
Emergency Action

The local fire brigade intervened (6 vehicles and 27 persons). The clearing of the emergency required to extract the hydrogen-air mixture, from the venting system. The fire department deployed an explosion-proof suction device. Using a hand diaphragm pump and suitable tools, several hundred litres of fluid were extracted and drained. It took more than three hours for the fire department to regain operational readiness.

Release Type
Release Substance
H2 100%
Hydrogen Release Concentration (%)
0.00
Ignition Source
References
References

News at https://www. 5min. at/5202405131641/chemieunfall-in-ligist-brachte-feuerwehren-in-alarmbereitschaft/ (accessed August 2025)