Explosion in a LH2 container
An explosion occurred in a Dewar used for metals tensile testing at liquefied hydrogen temperatures. The container consisted of vacuum insulated bottom and of cylindrical shaped polyurethane foam top. The venting of hydrogen was through a 2 inch diameter hole in the side of the foam insulation. The boil-off of liquid hydrogen was being accelerated by the use of two electric heaters on the bottom of the Dewar. Explosion was evaluated equivalent to about 0. 25 lb TNT. This was followed by the dispersion of hydrogen which resulted in further hydrogen-air explosions. [Ordin, NASA (1974)]
Record Quality Indicator
Event Initiating System
Classification of the Physical Effects
Nature of the Consequences

The INITATING CAUSE was the formation of a air-hydrogen mixture inside the Dewar. Air is believed to have backed into it through the vent hole in the polyurethane top. It was possible that air could have been cryo-pumped into it due to the high porosity of the foam. Ignition is believed to be caused by high surface temperature of heaters. The ROOT CAUSE was inadequate design of the system.