Explosion in a hydrogen purifier
During operation of a gaseous hydrogen purifier system, an explosion occurred when the valves were actuated to admit hydrogen. The purifier consisted of a precooler coil immersed in liquid nitrogen. [Ordin, NASA (1974)]
Record Quality Indicator
Event Initiating System
Classification of the Physical Effects
Nature of the Consequences
Causes

The system had not been completely purged because a valve in the system was not opened. This valve did not appear on the control panel schematic. The source of ignition not reported but was considered to be related to the high gas velocity at the inlet to tile adsorber coil.