Explosion at the hydrogen pumping station of a refinery
The event occurred in the hydrogen pumping station, placed between the hydrogen production unit (steam methane reformer) and the hydro-treatment unit. The second stage of the compressor cylinder released hydrogen into the confined compressor building, and which ignited. The failure was caused over-pressure in the piston, probably induced by ice blockage on the interstage cooler and the failure of the compressor housing heating system. A second explosion detached the roof building from the wall, and was attributed to backflow of naphtha and light hydrocarbon from the downstream hydro-treatment unit. Two other compressors were damaged.
Event Initiating System
Classification of the Physical Effects
Nature of the Consequences
Causes
Cause Comments
The INITIATING CAUSE was extreme cold weather, which CAUSEd i) ice blockage of the inter-stage cooler and ii) over-pressure in the compressor piston. However, the cold weather was expected and the plant had been designed considering very low temperatures. According to the referred scientific paper, the root CAUSE was an inadequate design, failing to identify critical facility and to guarantee for them safe and reliable operation.
