Explosion at a hydrogen furnace (718)

This data is from the European Hydrogen Incidents and Accidents database HIAD 2.1, European Commission, Joint Research Centre.

Explosion at a hydrogen furnace

Two employees were working on a electric furnace under hydrogen atmosphere that had jammed. The furnace exploded. The employees sustained flash burns to their faces and were taken to the hospital, where they were treated and released later the same day. The retrieval tool they were using was not suitable for servicing a hydrogen furnace, and may have been the ignition source for the explosion. The furnace had not been purged for 10 hours, as required by the manufacturer.
Event Date
December 5, 1998
Record Quality Indicator
Event Initiating System
Classification of the Physical Effects
Nature of the Consequences
Cause Comments
The furnace had not been purged for 10 hours, as required by the manufacturer.
Facility Information
Application Type
Application
Unknown
Specific Application Supply Chain Stage
Components Involved
Hydrogen furnace
Location Type
Operational Condition
Pre-event Summary
The furnace had not been purged for 10 hours, as required by the manufacturer. The retrieval tool the workers were using was not suitable for servicing a hydrogen furnace, and may have been the ignition source for the explosion.
Consequences
Number of Injured Persons
2
Number of Fatalities
0
Post-event Summary

They sustained flash burns to their faces and were taken to the emergency room at Petaluma Valley Hospital, where they were treated and released later the same day.

Lessons Learned
This is a case of incident caused by failing to follow existing procedures. Furnace operation, even in case of repairs, should strictly follow manufacturer's requirements. In particular, in presence of hydrogen in the system, effective purging is a critical step. Care should be taken in selecting retrieval tool avoiding them acting as ignition source.
Event Nature
Release Type
Release Substance
H2 100%
Hydrogen Release Concentration (%)
0.00
Ignition Source
Detonation
No
Deflagration
No
High Pressure Explosion
No
High Voltage Explosion
No
References
References

U. S. Department of Labor Occupational Safety & Health Administration OHSA incident report: https://www. osha. gov/ords/imis/accidentsearch. accident_detail?id=170764898