Explosion during hydrogen supply in a chemical company
This event occurred when a hydrogen-carrying trailer was supplying hydrogen to a chemical plant. Instead of filling the hydrogen stationary storage, large quantities of hydrogen were transferred from the trailer into the compressed air plant network. The explosive atmosphere ignited, exploded and opened a flange of the compressed air line, from which the hydrogen escaped and burned off. The cause was the confusion between hydrogen and compressed air connections: due to missing or unclear labelling, the trailer operator connected by mistake the trailer hydrogen outlet to the plant compressed air supply.
Event Initiating System
Classification of the Physical Effects
Nature of the Consequences
Cause Comments
The INITIATING/direct cause was the erroneous injection of hydrogen into a compressed air network, due to the confusion between hydrogen and compressed air connections. During operation, trailers were filled for various consumers. The design of the trailer connections was standardised only for the filling and emptying lines. Other connections, such as auxiliary media (compressed air) or analysis caps, were designed differently for each trailer. The incident occurred due to confusion between compressed air and sampling connections due to the mentioned different design of the analysis connection, similar to compressed air, on other trailers. On top of that, labelling was missing or unclear. The ROOT CAUSE was related to an inadequate risk assessment, which failed (1) to recognise the possibility of mixing up connections and (2) to deploy measures aiming to avoid it.