Skip to main content

Explosion during hydrogen supply in a chemical company (1089)

This data is from the European Hydrogen Incidents and Accidents database HIAD 2.1, European Commission, Joint Research Centre.

Explosion during hydrogen supply in a chemical company

This event occurred when a hydrogen-carrying trailer was supplying hydrogen to a chemical plant. Instead of filling the hydrogen stationary storage, large quantities of hydrogen were transferred from the trailer into the compressed air plant network. The explosive atmosphere ignited, exploded and opened a flange of the compressed air line, from which the hydrogen escaped and burned off. The cause was the confusion between hydrogen and compressed air connections: due to missing or unclear labelling, the trailer operator connected by mistake the trailer hydrogen outlet to the plant compressed air supply.
Event Date
October 27, 2022
Record Quality Indicator
Region / Country
Event Initiating System
Classification of the Physical Effects
Nature of the Consequences
Cause Comments
The INITIATING/direct cause was the erroneous injection of hydrogen into a compressed air network, due to the confusion between hydrogen and compressed air connections. During operation, trailers were filled for various consumers. The design of the trailer connections was standardised only for the filling and emptying lines. Other connections, such as auxiliary media (compressed air) or analysis caps, were designed differently for each trailer. The incident occurred due to confusion between compressed air and sampling connections due to the mentioned different design of the analysis connection, similar to compressed air, on other trailers. On top of that, labelling was missing or unclear. The ROOT CAUSE was related to an inadequate risk assessment, which failed (1) to recognise the possibility of mixing up connections and (2) to deploy measures aiming to avoid it.
Facility Information
Application
CGH2 tube trailer
Specific Application Supply Chain Stage
Components Involved
compressed air network
Storage/Process Medium
Location Type
Operational Condition
Consequences
Number of Injured Persons
0
Number of Fatalities
0
Environmental Damage
0
Property Loss (onsite)

0

Property Loss (offsite)

0

Post-event Summary

Damage to the compressed air pipeline and the silo

Lessons Learned
In this event, when transferring hydrogen from a hydrogen to a stationary storage, the personnel made the mistake to connect a hydrogen line to a compressed air line. Data on pressure are missing, nevertheless, it can be assumed for the pressure industrial standards, i. e. for hydrogen in the trailer a value between 200 and 300 bar, and for the compressed air a value below 10 bar. Therefore, hydrogen was released massively into the air pipelines, forming a flammable mixture. The confusion between lines at the basis of this event should be excluded (1) By design, i. e. a hydrogen line connector should not be compatible with any other gas lines connector, making mechanically impossible to create a working joint between different lines. And/or (2) By procedures, which requires clear guidelines, clear labelling of the lines and awareness among personnel of the hazards involved by the operations.
Event Nature
Emergency Action
Cooling of the pipes adjacent to the fire. Flushing the affected section of the compressed air system with clearance measurement. Flushing the silos containing the explosive mixture.
Release Type
Release Substance
H2 100%
Hydrogen Release Concentration (%)
0.00
Ignition Source
Detonation
No
Deflagration
No
High Pressure Explosion
No
High Voltage Explosion
No
References
References

Event from German database ZEMA https://www. infosis. uba. de/index. php/en/binaries/asset/zema_ereignis/31776/pdf (accessed December 2023)