Explosion in a cold rolling plant
Employees were trying to open the manhole cover (600 mm diameter) of a hydrofluoric acid tank with a grinder, when an explosion occurred. The explosion was probably caused by the presence of hydrogen formed by the acid attack of the metal. At the moment of the accident, the tank was empty, but uncleaned, and separated from the filling and ventilation pipes. According to the eMARS report (see references), in the course of cleaning work on the hydrofluoric acid storage tank, the residual of concentrated hydrofluoric acid remaining in the tank was diluted with water and not completely neutralized with sodium hydroxide. Subsequently, the container was sealed, after which the cleaning work was interrupted for at least two days. During this time, an explosive atmosphere formed in the tank, as a result of the reaction of the dilute hydrofluoric acid with the iron material of the container which produced hydrogen. When the cleaning work resumed, the explosive mixture was ignited presumably by the sparking due to the work with an angle grinder.
Event Initiating System
Classification of the Physical Effects
Nature of the Consequences
Cause Comments
The INITIATING cause was the ignition of the accidentally formed hydrogen insider the tank. A possible root cause of the accident would be the lack of risk assessment related to the potential formation of explosive atmosphere in the tank. Inadequate neutralisation of the residual acid and the disconnection of the tank from the venting line were contributing causes.