Accidental production of hydrogen from batteries
A release of hydrogen and steam occurred in the battery room of a nuclear power plant around 21 h. Site agents neutralised the batteries. Noting the failure of the smoke extractor, public firefighters ventilated the room.
Event Date
April 16, 2012
Record Quality Indicator
Event Initiating System
Classification of the Physical Effects
Nature of the Consequences
Causes

The INITATING CAUSE was the overheating of batteries, which produced th erelease of water of the electrolyte and hydrogen. The ROOT CAUSE is not provided. The fact that a fume detector, which had the obvious function to detect this type of events, was not fucntion suggests inadequacy of inspection and maintenance.