Agree that it's somewhat surprising that there isn't more research on flame impingement barriers. The Fire Codes are focused on fire resistance ratings, as opposed to impingement. Whereas these are important for building protection, and they offer some basis for reference, they don't necessarily address impingement issues which can be important and more pertinent for…
In the case of fuel-rich mixtures like those in the question, the heat of combustion for the mixture should be calculated on the basis of the oxygen content of the mixture. The heat of combustion per mole oxygen is twice the heat of combustion per mole hydrogen, i.e., it is 286*2 kJ per mole O2. You should be able to do the calculations based on this reply.
I am communicating with a company that is exploring this technology for an application involving a mixture of flammable gases, including hydrogen.
Neither section is a perfect fit for marine hydrogen fueling, but that is often the case with applying Codes. The most prudent approach is to draw from the most relevant provisions of both CFC Sections 2309 and 2310, disregarding requirements that clearly do not align with marine fueling practices. For example, CFC Section 2309 requires a vehicle to be parked on a concrete fueling pad…
This is a complex and sometimes contentious topic. The International Code Council (ICC) addresses hydrogen piping in the …
Generally speaking, the International Fire Code and NFPA 2 apply to non-transportation use of hydrogen. These are maturing quickly, with NFPA 2 currently having issued its most recent edition in 2023. Standards for both on-board LH2 tanks and LH2 tankers for bulk fuel transport are managed by the U.S. Department of Transportation (DOT) and are well established. DOT transport requirements for…
While HSP members have limited experience with MFCs in experimental setups, the Panel does not consider them to be reliable to provide a positive flow shutoff. For safety, a shutoff valve in series is recommended. Projects will also need to consider hazardous electrical rating and location when flowing H2. Regarding Coriolis mass flow measuring devices, Coriolis flow meters measure mass rate…
Regarding the concept of introducing hydrogen gas into natural gas pipelines, this is indeed a hot topic and there are recent quantitative treatments of fatigue crack growth driven by pressure cycling and potentially accelerated by hydrogen. Some analysis has shown that it can be acceptable to operate natural gas pipelines with a hydrogen blend. However, this is highly dependent…
It is possible to store large quantities of gaseous hydrogen above ground, but it will likely require a large footprint due to its relatively low density even at high pressure. Also, if the quantity equals or exceeds 10,000 lb., the facility will need to comply with OSHA 1910.119 process safety management requirements if located in the US. Similar regulations exist in Europe and Asia that…