Syngas fire at an ammonia production plant
The leak occurred at the ammonia reactor after a technical shutdown of 4 days. When the production was resumed and the syngas compressor restarted 14 hours later, a jet-fire occurred. The Internal Operation Plan was launched and the fire immediately extinguished. The cause of the gas release was a thermal dilatation difference between the joint and the reactor body. While the latter was still hot, the joint was cooled by the gas upon starting up the synthesis process. The high hydrogen concentration of the synthesis gas explains probably its spontaneous ignition. An additional cause was the procedure of quickly and completely exposing synthesis loop components to air by systematically opening all sectional valves, even in the event of short-term shutdowns, increased the unit’s vulnerability to this type of incident.
Event Initiating System
Classification of the Physical Effects
Nature of the Consequences
Cause Comments
The INITIATING cause was the loss of containment of the syngas due to thermal gradients between joint and reactor, and the spontaneous ignition of the gas. Contributing cause was the shutdown procedure which opens all the valves, which exposes to air the whole ammonia synthesis loop. In conclusion, root cause would be probably a deficiency in the design of the operation procedures