Small release from a LH2 tanker
A liquid hydrogen tanker was travelling to a customer when the driver noticed that hydrogen release was occurring at the trailer vent stack. The driver stopped the vehicle in a safe location and investigated the cause discovering that the vent valve had opened slightly. The driver could stop the venting by closing the valve tightly. The tanker could deliver at destination without further venting (total trip approximately 3 hours). Back to the home terminal, an inspection found that a small amount of ice had most likely prevented full closure of the vent valve. This ice formation had occurred when equilibrating internal pressure before the start of the trip. When the ice melted during the travel, the vent opened slightly, resulting in a venting.

The INITIAL CAUSE a not tight manual vent valve. The ROOT CAUSE was th formation of ice during prearation of the load for the trip. This ould hint at incomplete procedural guidelines.