Liquid hydrogen tank explosion
A rupture disc opened on a 76 m3 (20,000-gallon) liquid hydrogen tank, causing the vent stack to release cold gaseous hydrogen. The gas ignited causing a fire on the vent stack's outlet. Emergency responders intervened by removing the remaining hydrogen but left a small volume which could not be removed manually. During this operation, the vacuum system lost its heat isolation capacity due to a (mechanical?) failure. This triggered a rapid evaporation of the residual liquid hydrogen with consequent increase of the tank internal pressure. In answering to this, the emergency responders sprayed the tank with water and directed a stream onto the fire exiting the vent stack. The water jet was pointed directly into the open vent stack, thus interacting with hydrogen vapours from the residual hydrogen (between −253 °C and −241 °C). This caused the water to freeze in the vent stack. This ice blocked the stack, which was the only exit for the cold hydrogen gas. Eventually, all residual hydrogen in the tank warmed up, causing the tank to over-pressurize and rupture with an explosion known as a BLEVE (Boiling Liquid Expanding Vapour Explosion).

The INITIATING CAUSE was the opening of the burst disc. It is unclear if this was triggered by a material failure or by an increase of the tank internal pressure beyond the design pressure of the disc. The incident escalated to an explosion (BLEVE) due to wrong decisions/actions of the emergency responders, to which probably contributed the lack of emergency procedures of the plant, up to a lack of proper risk assessment. These consideration point at a shortcoming in the safety management as ROOT CAUSE.