Liquid hydrogen release from a truck
The leak occurred on a 44 m³ vehicle of liquid hydrogen during a delivery to the unloading station of a steel plant. The truck drivers had connected the tank container to the fixed storage managed by a subcontractor, carried out a nitrogen sweep of the hose before cooling it, and were pressurizing the hydrogen before unloading when they saw a white cloud. The drivers closed the bottom valve of the container and the upstream and downstream valves of the heater before evacuating the area and sounding the alarm. Two technicians of the subcontractor company arrived 30 minutes later, located the leak on the flange of one of the four protective valves of the tank container. Two of the four fixing bolts were missing from the leaking flange. The technicians closed the three ways valve which allowed to isolate the valves 2 by 2. They could then re-seale the flange correctly and performe a leak test.
Event Initiating System
Classification of the Physical Effects
Nature of the Consequences
Causes
Cause Comments
The INITIATING cause was the lack of tightness of a cryogenic tank flange, which started releasing when raising the pressure,. The root cause was inadequate reassembling of some of the flange bolts during the previous maintenance, performed 17 days before.