Liquid hydrogen release from a rail tanker
The whole content of the rail tanker, that is 42,000 l (about 3000 kg) of liquid hydrogen, was entirely lost over a period of seven hours via the venting line of a tank. The accident occurred at a railway station, and the wagon with the tank that had been uncoupled from the goods train and shunted to a siding to allow the release of its content. The cryogenic tank was of the Dewar type with numerous insulating and reflecting layers in its inter-space, kept under vacuum. According to the source referenced, a micro-crack in the outer wall of the tank caused the loss of the vacuum and was the initiating event of the release. The crack caused the loss of the interspace vacuum and of the related thermal insulation function, with a quick increase of the conductive and convective heat transfer between the tank interior and the environment. The liquid and vapour hydrogen raised the internal pressure to the design value of the safe valves (4). The valves are designed to maintain a constant 12 bar pressure differential between the upstream and downstream sides of their shutter (thus the max pressure attained inside the tank during the accident was 13 bar). The calculations of the referred source (Cancelli et al. , Cryogenics 2004) shows that: 1. The hydrogen temperature raised slowly for the first 2. 5 hours, until the moment it reached the critical temperature (Tc). Until that time, the incoming heat was used as latent vaporisation heat. After the attainment of Tc, the incoming heat became sensible heat and the temperature raised steeply. 2. The hydrogen flow rate through the safety valves peaked approximately at the same moment (approximately after 2. 5 h), corresponding to the moment in which the densities of the gas and liquid phases in equilibrium become similar.
Event Initiating System
Classification of the Physical Effects
Nature of the Consequences
Causes
Cause Comments
The loss of vacuum and of the related thermal insulating capacity of the cryogenic tank was due to the cracking of the external layer. It is unknown if the crack was caused by the collision with an object, or a design-related event (for example too high local stresses)