LH2 tank cracking
During transfer of LH2 from a 200,000 gallon (760 m3) storage vessel to a road trailer, loss of vacuum was detected due to a crack in the outer vessel. The crack was located below an elbow of the 6” diameter pressurisation line. The probable cause of the crack was the formation of liquid air dripping onto the outer vessel. [Ordin, NASA (1974)]
Record Quality Indicator
Event Initiating System
Classification of the Physical Effects
Nature of the Consequences

The INITIATING CAUSE was the failing of outer thermal shield of the vessel, due to thermal cold shock. During the transfer operation liquid air formed on the vertical run of the pressurisation line, ran down the pipe and then dripped of the elbow onto the vessel. The vertical run did not have drip trays to collect liquid air and the crack formed where the liquid air dropped. Probable ROOT CAUSE was an installation error (a missing drip tray supposed to be there) or a design error (a not-foreseen safety component).