Leak from a hydrogen compressor
This incident occurred on a high-pressure hydrogen compressor part of the hydrogen production and storage unit of a testing laboratory. While in operation, a hydrogen gas detector installed above the compressor room detected a hydrogen concentration of 2,000 ppm, automatically shutting down the hydrogen compressor and closing the shutoff valve. When the concentration in the room was confirmed below 2000 ppm, an employee entered the room and identified the location of the leak on the leak port of the cylinder cap of the compressor. An overhaul inspection had been conducted one month before, and in that occasion, O-rings had been replaced. The leak was caused by the corrosion caused by remnant of the soap used in the tightness test performed during the inspection.

The INITIATING CAUSE was the damaging of a O-ring and its seat, which could guarantee no more their sealing function. After dismantling the compressor cylinder, the investigators found scratches on the upper inner surface of the cylinder and cracks in the cylinder cap O-ring. These were attributed to the presence of the soap water used in tightness tests. The eight connecting joints between the cylinder and cylinder cap of the ultra-high-pressure hydrogen compressor were annually tested for airtightness using soapy water. Because the soap water was retained in the structure, corrosion occurred near the O-ring grooves (atmospheric side) of the cylinder and cylinder cap. The corrosion was not discovered before because the affected corroded area was not subject to periodic inspection. The same phenomenon was found in all eight cylinders opened after the accident, although variations occurred among the cylinders. It is believed that corrosion of the O-ring grooves restricted the movement of the backup ring, causing the bias-cut portion of the backup ring to come into contact with the O-ring and damage it. Therefore, the ROOT CAUSE can be attributed to some blind-spot of shortcoming of the maintenance procedures.