leak from a dispenser of a mobile HRS (1208)

This data is from the European Hydrogen Incidents and Accidents database HIAD 2.1, European Commission, Joint Research Centre.

leak from a dispenser of a mobile HRS

The accident occurred at a mobile hydrogen station during a fuelling test for a fuel cell vehicle. The day before, the gas detector in the dispenser detected a leak and the equipment was shut down. With a mobile detector and a helium leak test, the leak was found coming from the emergency shutdown valve of the dispenser. The valve manufacturer replaced the O-ring. The day after during a fuelling test, a leak was detected again. The leakage point was and found on the lower part of the emergency disconnect coupler on the fuelling nozzle side of the fuelling hose was leaking.

Event Date
October 6, 2015
Record Quality Indicator
Event Initiating System
Classification of the Physical Effects
Nature of the Consequences
Causes
Cause Comments

The INITIATING CAUSE was a small release of hydrogen from a damaged O-ring. The ROOT CAUSE could not be identified with certainty and was believed to be one of the following: 1. The O-ring of the coupling valve was damaged during the previous work of dismantling and remounting of the emergency valve. 2. The sealing of the coupling was poor and during fuelling the application of a force on the coupling could have caused the movement and the damage of the O-ring.

Facility Information
Application Type
Application
70 MPa HRS
Specific Application Supply Chain Stage
Components Involved

emergency valve, dispenser

Storage/Process Medium
Actual Pressure
82
Design Pressure
82
Location Type
Location description

DESCRIPTION OF THE FACILITY High-Pressure Gas Production Capacity: 12,366 m3/day Normal Operating Pressure: 70. 0 MPa Normal Operating Temperature: -40 to 40°C The location is classified as CONFINED, because the leaking valve was installed in an enclosed section of the dispenser.

Operational Condition
Pre-event Summary

10 days before, a safety inspection was terminated and the operation restarted 3 days after. 10 vehicles had already been refuelled, when the first leak was detected during the refuelling of the 4th FCV of the day.

Consequences
Number of Injured Persons
0
Number of Fatalities
0
Environmental Damage
0
Post-event Summary

No personal injury, no property damage. Only a very small release of hydrogen.

Lessons Learned

This event is classified as incident because of the hydrogen release and the resources spent in improving the situation; however, considering that the safety system functioned as designed and that the leak was very small, system it is borderline with a near-miss classification. The KHK report indicated that only at the lowest temperature of -40°C, the leak rate exceeded \the max allowed rate (2. 1 10-5 Pa m3/s, instead of a max of 1. 0 10-5 Pa m3/s). The following general conclusion van be drown (modified in respect to the original KHK report): (1) Leak testing is essential to detect any leaks before fuelling. However, as demonstrated by a similar incident (see HIAD_1207), they are not always effective in detecting loss of confinement if the conditions under tests differ too much from those experienced during refuelling. Leaking rate measured at room temperature were according to specification, while at -40 C resulted above maximum allowed. (2) It is necessary to consider the whole assembly of the emergency disconnect coupler, the hose and fuelling nozzle, and the external force acting on them, to prevent that any force not considered in the design from being applied to the emergency disconnect coupler. (3) An effective seal management is crucial in high-pressure gas equipment. This implies the correct choice and management of O-rings, with sealing power also at lower temperature and in a wide range of dynamic pressure. Moreover, correct control and care of the seal surface is important during the installation and replacement.

Event Nature
Emergency Action

1. September 25: Completed inspection 2. September 28: Start of operation 3. October 5: During hydrogen fueling to the 4th vehicle (10th since the start of operation) (Temperature: -37°C, Pressure: 63 MPa), the hydrogen gas leak detection alarm device inside the dispenser activated. After detecting the leak, the hydrogen inside the piping was automatically depressurized and released from the vent. The leakage point was investigated using a portable hydrogen gas detector, but it was not identified. (This is a separate hydrogen leakage accident from the one mentioned above. ) 4. October 6: Under the supervision of the equipment manufacturer, the leakage point was thoroughly investigated, and it was confirmed that the shut-off valve inside the dispenser was leaking. 5. October 6: The O-ring of the shut-off valve inside the dispenser was replaced, and during the hydrogen fueling test to a fuel cell vehicle (Temperature: -37°C, Pressure: 55 MPa), the hydrogen gas leak detection alarm device inside the dispenser activated. The leakage point was investigated using a portable hydrogen gas detector, and it was confirmed that the lower part of the emergency disconnect coupler on the fueling nozzle side of the fueling hose was leaking.

Release Type
Release Substance
H2 100%
Hydrogen Release Concentration (%)
0.00
Ignition Source
References
References

KHK accidentl database, incident 2015-363: https://www. khk. or. jp/public_information/incident_investigation/hpg_incident/gen_lp. html (accessed august 2024)

Translated version in English (by GPT@JRC)