leak from a dispenser of a mobile HRS
The accident occurred at a mobile hydrogen station during a fuelling test for a fuel cell vehicle. The day before, the gas detector in the dispenser detected a leak and the equipment was shut down. With a mobile detector and a helium leak test, the leak was found coming from the emergency shutdown valve of the dispenser. The valve manufacturer replaced the O-ring. The day after during a fuelling test, a leak was detected again. The leakage point was and found on the lower part of the emergency disconnect coupler on the fuelling nozzle side of the fuelling hose was leaking.
Event Date
October 6, 2015
Record Quality Indicator
Event Initiating System
Classification of the Physical Effects
Nature of the Consequences
Causes

The INITIATING CAUSE was a small release of hydrogen from a damaged O-ring. The ROOT CAUSE could not be identified with certainty and was believed to be one of the following: 1. The O-ring of the coupling valve was damaged during the previous work of dismantling and remounting of the emergency valve. 2. The sealing of the coupling was poor and during fuelling the application of a force on the coupling could have caused the movement and the damage of the O-ring.