leak from a dispenser of a HRS
The accident occurred during the filling of hydrogen into a fuel cell vehicle (FCV) at a hydrogen station. The gas detector in the dispenser detected a leak, and the equipment was shut down. A test was performed, but it was unable to find a leak. A filling test was then executed, and the leak was finally identified on the emergency shutdown valve. The tightening torque of the emergency shutdown valve was checked, and it was found to be below the specified value.
Event Date
May 23, 2016
Record Quality Indicator
Event Initiating System
Classification of the Physical Effects
Nature of the Consequences

The INITIATING CAUSE was a small release of hydrogen from a valve. The ROOT CAUSE could not be identified with certainty, and was believed to be one of the following: 1. Loosening of the tightening torque: The tightening torque may have decreased due to temperature and pressure changes or external vibrations, resulting in a leak. 2. Performance of the emergency shutdown valve: The valve may have been defective due to manufacturing defects or damage during assembly.