Hydrogen release and explosion on a compressor of a refinery
An explosion took place at the hydrodesulphurisation unit of a refinery's crude oil. A leak occurred on suction line of a hydrogen compressor used for the re-circulation of the hydrogen required for the desulphurisation process. The compressor was in a room without ventilation, the hydrogen cumulated there creating an explosive mixture which ignited. The unit's alarm was immediately triggered in the control room and the operator activated the internal emergency plan. The site's firefighting team went to the site and brought the following fire under control. The external fire fighters service did not need to intervene. The accident caused two fatalities and five injuries among the workers. According to one of the sources, the plant supervisor sent personnel to investigate. it is not clear if this was the cause of the fatalities and injuries. The explosion was heard at 12 km distance. The operation of the unit affected by the accident were stopped as well as the neighbouring thermal cracking unit, while the operation of 30 units of the refinery have continued their operation.
Event Initiating System
Classification of the Physical Effects
Nature of the Consequences
Cause Comments
The INITIATING CAUSE was probably a hydrogen leak on a compressor for the re-circulation of the hydrogen. The leaking element was a gasket on the suction line of the compressor, which had been installed at the commissioning of the facility, 9 years before, and had never been inspected or replaced. The consequences of the leak and ignition were serious, because the explosion occurred in a confined space. To the ROOT CAUSE contributed factor such as: (1) failing to inspect and maintain critical components, (2) ill design of the compressor room, (3) lack of safety awareness among personnel and the management. The origin of all this was probably a lack of proper risk assessment and proper safety management.