Hydrogen leak in a refinery
The leak occurred at an heat exchanger of the hydro-isomerisation unit of a refinery. Following the observation of a pressure drop between two heat exchangers, controls were carried out on site. A noise was heard, indicating a gas leak, but its location could not be not identified. The gas detectors installed on the unit did not activate. The access to the unit was forbidden and emergency services and the fire department alerted. The unit was decompressed using the safety flare. When the pressure was sufficiently reduced, two operators looked for the origin of the leak. They located it on a flange at the level of a heat exchanger/beam gasket. The line was depressurized under nitrogen. The flange was leaking to the a pressure drop accompanied by a rise in temperature between the 2 exchangers, causing fragility to the flange assemblies. The hydrogen leak is estimated at 100 kg. When the bundles of the 2 exchangers were dismantled, it was then noticed that the baffles were mounted upside down on the 2 exchangers (baffles not mounted in the direction of fluid flow: baffles located on the outlet and not on the inlet of the load). Maintenance on these exchangers had been carried out during the previous major shutdown. The deflectors were deformed at the tube plate. In addition, an imprint of the outlet line of the heat exchanger on the deflector was noted. The deflectors are repositioned in the good direction and reintroduced in their respective heat exchanger.
Event Initiating System
Classification of the Physical Effects
Nature of the Consequences
Causes
Cause Comments
The INITIATING CAUSE was the loss of sealing capacity of a gasket on a flange of the heat exchanger. The baffles inside the two heat exchangers were wrongly mounted after a maintenance step during the last shutdown. This had probably an impact on the behaviour of the connecting pipe between the two heat exchangers and lead to a weak point on the gasket. The ROOT CAUSE was wrong installation due to inadequate application of the maintenance procedures.