Hydrogen fire from a gas pipeline in a nuclear power plant
A hydrogen fire occurred in a nuclear power plant outside the controlled area. The leaking point was on a pipe system of the distribution circuit of the gas network (6 bar nominal working pressure). The specific location was a joint on the fire-protection cupboard containing the hydrogen cylinders. The fire started during a repairing intervention on a cupboard nearby, performed by a sub-contractor using a hot surface welding equipment. Internal emergency services isolated and depressurized the pipes, and extinguished the flame.
Event Initiating System
Classification of the Physical Effects
Nature of the Consequences
Causes
Cause Comments
INITIATING CAUSE was the local leak from a hydrogen pipeline and its ignition by welding works. ROOT CAUSE, as reported by the ASN report referred to, is the lack of risk assessment (analysis, implementation) related the temporary modification of the hydrogen distribution system (a nitrogen line).