Hydrogen explosion at a refinery
The accident occurred at a distillate dewaxing Unit (MDDW) of the refinery, during the operation of regeneration of the catalyst. To perform this operation, both temperature and pressure have to be increased. After approximately six hours after having reached the correct regeneration conditions, the 10 inches pipe at the bottom to one of the two reactor experienced a guillotine break, and hot gas was released from both ends. The gas released consisted of 81% of hydrogen, 9. 5% of methane and some light hydrocarbons. It rapidly ignited (0. 7 sec), causing an explosion. A shock wave from the resulting explosion expanded through the adjacent neighbourhood, causing varied degrees of blast damage to residential homes. The ensuing flash fire spread up to 230 feet west of the tank farm.
Event Date
November 4, 2009
Record Quality Indicator
Region / Country
Event Initiating System
Classification of the Physical Effects
Nature of the Consequences
Cause Comments
The INITIATING cause of the accident was the corrosion of pipe, inducing thinning of the pipe wall. The corrosion went uninspected for years. The metallurgical analysis (see references) identified the same kind of suffixation corrosion already found in accidents in other plants; sulphur compounds in the process stream corroded a steel piping segment, causing the pipe walls to become severely thin. While sulfidation is a well-known damage mechanism at refineries that requires regular inspection and monitoring, the segment that failed has no record of ever being inspected. This suggests a ROOT CAUSE related to lack of effective maintenance and inspection procedures and to management shortcoming.