Hydrogen explosion in a refinery
The explosion occurred when a spark from welding equipment ignited flammable vapours from a 415,000-gallon (ca. 1. 5 million of litres) sulphuric acid storage tank at the refinery. The investigation showed that the explosion was caused by the ignition of hydrogen leaking from the tank as result from years of neglect. Hydrogen is produced when sulphuric acid comes into contact with the steel tanks. One worker was killed and eight other workers were injured. The surrounding sulphuric acid tank farm was heavily damaged in the blast, and an estimated 1. 1 million gallons of the acid were released into the environment, including nearly 100,000 gallons (400000 l) that flowed into the river.
Event Initiating System
Classification of the Physical Effects
Nature of the Consequences
Cause Comments
The INITIATING cause was the ignition of hydrogen leaked from H2SO4 tanks. The root cause was failure to maintain and inspect the tanks, due to the lack of a safety and risk management plan. Contributing cause was the loss of containment of the tanks due to corrosion and formation of gaseous hydrogen .