Hydrogen explosion in a metal processing pla
The event took place at the metal sheet pre-heating oven of a galvanization unit. This was using a mixture of hydrogen and nitrogen to form a reducing atmosphere and avoid oxydation of the metallic sheets. The zinc crucible’s draining operations was completed and the hydrogen purge operation which had been started 6 hours earlier, was underway when an explosion happened.
Event Initiating System
Classification of the Physical Effects
Nature of the Consequences
Causes
Cause Comments
The INITIATING CAUSE was due to the fact that the valve on the backup hydrogen tank and the by-pass on the furnace’s supply line were not closed. A hot spot in the oven probably ignited the explosive atmosphere. No information is available on the ROOT CAUSE, but probably related to shortcomings of the procedures and/or an operator error.