Skip to main content

Hydrogen explosion in a metal processing pla (106)

This data is from the European Hydrogen Incidents and Accidents database HIAD 2.1, European Commission, Joint Research Centre.

Hydrogen explosion in a metal processing pla

The event took place at the metal sheet pre-heating oven of a galvanization unit. This was using a mixture of hydrogen and nitrogen to form a reducing atmosphere and avoid oxydation of the metallic sheets. The zinc crucible’s draining operations was completed and the hydrogen purge operation which had been started 6 hours earlier, was underway when an explosion happened.
Event Date
July 25, 2005
Record Quality Indicator
Region / Country
Event Initiating System
Classification of the Physical Effects
Nature of the Consequences
Cause Comments
The INITIATING CAUSE was due to the fact that the valve on the backup hydrogen tank and the by-pass on the furnace’s supply line were not closed. A hot spot in the oven probably ignited the explosive atmosphere. No information is available on the ROOT CAUSE, but probably related to shortcomings of the procedures and/or an operator error.
Facility Information
Application Type
Application
generic metal processing
Specific Application Supply Chain Stage
Components Involved
Pre-heating oven for metal sheets
Storage/Process Medium
Location Type
Operational Condition
Pre-event Summary
The oven had been shut down the previous evening for annual maintenance work.
Consequences
Number of Injured Persons
0
Number of Fatalities
0
Post-event Summary

The four employees present were not injured. No impact outside the site was reported.

Event Nature
Emergency Action
probably none,due to the velocity of the event.
Release Type
Release Substance
H2 N2
Hydrogen Release Concentration (%)
0.00
Ignition Source
Detonation
No
Deflagration
No
High Pressure Explosion
No
High Voltage Explosion
No
References
References

Event No, 30365 of the French database ARIA https://www. aria. developpement-durable. gouv. fr/accident/30365/ (accessed December 2020)