Hydrogen explosion in a LH2 storage tank (28)

This data is from the European Hydrogen Incidents and Accidents database HIAD 2.1, European Commission, Joint Research Centre.

Hydrogen explosion in a LH2 storage tank

A combustion event occurred in a liquid hydrogen tank (LH2) under a high pressure and in presence of 12 m³ (700 kg) of LH2, at a testing site for space equipment. A pressurisation test was being performed when a high pressure combustion took place inside the tank. the liquid H2 tank was pressurised by a control device up to 250 bar in 30 sec. When the pressure in the tank reached 160 bar, a noise indicating a pressure drop was observed and the detectors recorded a pressure fluctuation of 10 bar. The sudden and significant fluctuations of the measured parameters (temperature of wall, pressure, flow) brought to the termination of the test. The stop did not have consequences. The cause of the accident was the presence of combustion of frozen oxygen in an blind branch of the tank’s drain pipe. Its presence was probably due to the partial unsuccessful purging by helium, which had not been able to purge the air contained in the blind pipe, because placed in the lower part of the tank. The trapped air had re-solidified when while refilling the tank with LH2. Several combustion spots were detected: in condensed phase between solid O2 and H2 gas, in less dense phase between H2 and O2 gas. The combustion was undoubtedly triggered by the friction of the pellets against the walls and the adiabatic compression of the H2/O2 gas mixture.
Event Date
December 4, 1991
Record Quality Indicator
Region / Country
Event Initiating System
Classification of the Physical Effects
Nature of the Consequences
Cause Comments
The INITIATING CAUSE INITIATING CAUSE was the presence of air/oxygen in a blind branch of a pipe, due to unsuccessful purging of the tank before refilling with LH2. The ROOT CAUSE could b identified in an ineffective purging procedures, as well as in a design mishap due to the presence of blind section of pipes.
Facility Information
Application Type
Application
Aerospace
Specific Application Supply Chain Stage
Components Involved
liquid hydrogen cryogenic tank
Storage/Process Medium
Storage/Process Quantity
700
Actual Pressure
16
Design Pressure
25
Location Type
Location description
The event occurred at a testing centre for propulsion system aerospace (rockets). It was in an isolated area with no admittance to the public. The cryogenic LH2 tank nominal capacity was 12 m3 correspomding to 700 kg of hydrogen, with a nominal working pressure of 250 bar (MAWP 400 bar). The testing setup was complete with a liquid oxygen tank and a tank containing gaseous hydrogen up to 800 bar.
Operational Condition
Pre-event Summary
Few months before, the test tank had been emptied and purified (by injecting helium) as the hydrogen gas network was suspected of being polluted due to an intake of air from a compressor, one year before.
Consequences
Number of Injured Persons
0
Number of Fatalities
0
Environmental Damage
0
Property Loss (offsite)

0

Post-event Summary

no consequence to person or equipment

Lessons Learned
This was a near miss, and process control system worked as designed, able to detect on time an abnormal situation thanks to the signal sent by the sensors measuring process parameters. On top of the need for improvement of tank design, this near miss highlighted also the need to understand better the behaviour of liquid hydrogen in presence of impurities.
Event Nature
Emergency Action
The emergency action was limited to stopping the pressurisation test and to de-pressurising the tank.
Release Type
Release Substance
H2 100%
Hydrogen Release Concentration (%)
0.00
Ignition Source
Detonation
No
Deflagration
No
High Pressure Explosion
No
High Voltage Explosion
No
References
References

ARIA event https://www. aria. developpement-durable. gouv. fr/accident/26618/

Retour d'expérience issu de la mise en oeuvre d'un réservoir d'hydrogène liquide haute pression Journée technique INERIS, du 7 octobre 2003