Hydrogen explosion in a LH2 storage tank
A combustion event occurred in a liquid hydrogen tank (LH2) under a high pressure and in presence of 12 m³ (700 kg) of LH2, at a testing site for space equipment. A pressurisation test was being performed when a high pressure combustion took place inside the tank. the liquid H2 tank was pressurised by a control device up to 250 bar in 30 sec. When the pressure in the tank reached 160 bar, a noise indicating a pressure drop was observed and the detectors recorded a pressure fluctuation of 10 bar. The sudden and significant fluctuations of the measured parameters (temperature of wall, pressure, flow) brought to the termination of the test. The stop did not have consequences. The cause of the accident was the presence of combustion of frozen oxygen in an blind branch of the tank’s drain pipe. Its presence was probably due to the partial unsuccessful purging by helium, which had not been able to purge the air contained in the blind pipe, because placed in the lower part of the tank. The trapped air had re-solidified when while refilling the tank with LH2. Several combustion spots were detected: in condensed phase between solid O2 and H2 gas, in less dense phase between H2 and O2 gas. The combustion was undoubtedly triggered by the friction of the pellets against the walls and the adiabatic compression of the H2/O2 gas mixture.
Event Initiating System
Classification of the Physical Effects
Nature of the Consequences
Causes
Cause Comments
The INITIATING CAUSE INITIATING CAUSE was the presence of air/oxygen in a blind branch of a pipe, due to unsuccessful purging of the tank before refilling with LH2. The ROOT CAUSE could b identified in an ineffective purging procedures, as well as in a design mishap due to the presence of blind section of pipes.