Hydrogen explosion at an aerospace company
The event occurred in a support building at a test stand complex. The explosion destroyed two support buildings and severely damaged a large amount of equipment. No one was injured. Gaseous hydrogen leaked into one of the support buildings from a high pressure hydrogen gas system consisting of two storage tanks and connecting pipes. A location at one pipe had been attacked by galvanic corrosion on the outer wall for some time, thinning the wall. However, the pipe was not routinely under pressure. Just before the explosion, an isolation valve failed open, permitting hydrogen under a pressure of ca. 30 MPa (4300 psig) to enter the pipe and break the thinned wall. Hydrogen from the two 19. 8 cubic meter (700 cubic foot) tanks was released into one support building and into the next one. An electrical contact in a sump pump motor starter relay arced when the sump pump in the first building began an automatic start sequence. The electrical arc ignited the hydrogen in one building and this explosion apparently initiated an explosion in the other building.
Event Date
October 31, 1980
Record Quality Indicator
Region / Country
Event Initiating System
Classification of the Physical Effects
Nature of the Consequences
Cause Comments
INITIATING CAUSE was the failure of a high pressure valve into a low pressure pipe system with corroded wall, which failed as well. ROOT CAUSES were (i) the wrong choice of the steel type for the piping, (ii) the lack of assessment of the extension of corrosion, (iii) lack of preventing safety measures, (iv) lack of inspection and maintenance procedures. In general, a lack of capacity by management to manage safety of the facility, and managing changes.