Flash fire when disconnection a hydrogen barge
While a LH2 barge was being disconnected from dock, a flash occurred in the vent stack. No damage occurred but potential existed for major damage. [Ordin, NASA (1974)]
Record Quality Indicator
Event Initiating System
Classification of the Physical Effects
Nature of the Consequences

The INITIATING CAUSE was the premature activation of a burst disc. The LH2 burst disk was found to have a series of pin holes which permitted gaseous hydrogen to enter the land vent line. An explosive mixture was formed when air entered the disconnected The ROOT CAUSE could be a manufacturing error or a lack of adequate inspection.