fire at the vent stack of a hydrogen production plant
A fire at the exit of the vent line occurred when filling a tube trailer. An employee suspected a flame at the outlet of the hydrogen venting line during the filling of a trailer. , by sawing the air shimmering around the blowout. The operator made a plant shutdown and tried to find out the cause. Since the vent line was collecting hydrogen streams from several units at different pressures, the provenience of the vented hydrogen was not easy identifiable. They found a not fully closed hand valve. It was a venting valve from the trailer filling station. After closing it, they discovered no further problem, restarted the plant and continued to fill the trailer. The inspectors confirmed the occurrence of a flame based on clearly visible tempering colours at the blowout of the vent line. They found also a plate mounted at the blowout, which was not foreseen by the original design. It had been installed to impede bird nesting. It is probable that the increased flow of hydrogen at the vent caused by the left open valve, was ignited by the sharp edge of the plate.
Event Initiating System
Classification of the Physical Effects
Nature of the Consequences
Cause Comments
The INITIATING CAUSE of the accidental release was a valve left partially open. The ROOT CAUSE could be attributed to the difficulty for the operator to check if the valve was fully closed. A contributing factor was the ignition of the vented hydrogen, probably due to the mounting of a metallic plate (not foreseen in the original vent design) at the blowdown location.