Fire on a valve of a hydrogen pipe network
At a chemical processing plant, a release of pressurised hydrogen gas resulted in an explosion and fire injuring lightly three workers and causing damage to plant. The incident occurred during the recommissioning of equipment after routine scheduled maintenance. The release was caused by the failure of a butterfly valve under a hydrogen of approximately 2000 kPa (20 bar), due probably to wrongly installed bearing during the maintenance. The event had the potential to cause a more significant adverse effect.
Event Date
September 17, 2023
Record Quality Indicator
Event Initiating System
Classification of the Physical Effects
Nature of the Consequences

The INITIATING CAUSE was the release of hydrogen caused by the failure of a valve. The bearing bush bolts of the butterfly valve may not have been correctly installed at the time of overhaul resulting in separation of valve bearing bush. The local authorities identified the following key issues: (1) High pressure valves must be quality checked for correct assembly post maintenance overhauls. (2) Effective systems and processes that ensure quality assurance must be used for the overhaul and testing of the valves to prevent failure of such valves. (3) The maintenance of the equipment involved in hydrogen usage must comply with Original Equipment Manufacturer (OEM) specifications. The ROOT CAUSE may then be identified in shortcomings in the execution of the maintenance. Nevertheless, a component may lay in material defects.