Fire on a valve of a hydrogen pipe network (1095)

This data is from the European Hydrogen Incidents and Accidents database HIAD 2.1, European Commission, Joint Research Centre.

Fire on a valve of a hydrogen pipe network

At a chemical processing plant, a release of pressurised hydrogen gas resulted in an explosion and fire injuring lightly three workers and causing damage to plant. The incident occurred during the recommissioning of equipment after routine scheduled maintenance. The release was caused by the failure of a butterfly valve under a hydrogen of approximately 2000 kPa (20 bar), due probably to wrongly installed bearing during the maintenance. The event had the potential to cause a more significant adverse effect.

Event Date
September 17, 2023
Record Quality Indicator
Event Initiating System
Classification of the Physical Effects
Nature of the Consequences
Cause Comments

The INITIATING CAUSE was the release of hydrogen caused by the failure of a valve. The bearing bush bolts of the butterfly valve may not have been correctly installed at the time of overhaul resulting in separation of valve bearing bush. The local authorities identified the following key issues: (1) High pressure valves must be quality checked for correct assembly post maintenance overhauls. (2) Effective systems and processes that ensure quality assurance must be used for the overhaul and testing of the valves to prevent failure of such valves. (3) The maintenance of the equipment involved in hydrogen usage must comply with Original Equipment Manufacturer (OEM) specifications. The ROOT CAUSE may then be identified in shortcomings in the execution of the maintenance. Nevertheless, a component may lay in material defects.

Facility Information
Application Type
Application
Unknown
Specific Application Supply Chain Stage
Components Involved

bearing ,valve

Storage/Process Medium
Actual Pressure
2
Location Type
Operational Condition
Pre-event Summary

Event happed at the re-start of operations after scheduled maintenance

Consequences
Number of Injured Persons
3
Number of Fatalities
0
Environmental Damage
0
Property Loss (offsite)

0

Post-event Summary

Three injured workers: two were recommissioning the equipment, and a third was a store worker approximately at 40 m from the location of the release. The injured workers did not require hospitalisation.

Lessons Learned

The local authorities issued the following recommendations. All Site Senior Executives should: (1) Remember that hydrogen is considerably more hazardous than liquid petroleum gas (LPG), as it possesses a wider explosives range, and the ignition energy is approximately 13 times lower than that of the LPG. Further, the low viscosity and small size of a hydrogen molecule create the potential for gradual dispersion through the atomic matrix of solid metal, such as pipework, leading to additional challenges in containing hydrogen. (2) Employ highly sensitive and specialised detection method, as detecting hydrogen gas leaks can present difficulties, particularly due to its tendency to disperse rapidly. (3) Refer to OEM specifications to ensure work methods and testing procedures are suitable for application, when working on a hydrogen equipment. (4) Ensure suitable trained personnel are engaged in maintenance and quality assurance. [Note of HIAD Validator: it is unclear if these recommendations were triggered by safety-shortcoming findings specific to this event, or if they are general recommendations issued in all cases]

Event Nature
Release Type
Release Substance
H2 100%
Hydrogen Release Concentration (%)
0.00
Ignition Source
References
References

Government of Western Australia, report 01/2016 https://www. worksafe. wa. gov. au/publications/dangerous-goods-safety-significant-incident-report-no-01-16-and-petroleum-safety (accessed September 2025)

Also mentioned in Wikipedia https://en. wikipedia. org/wiki/Hydrogen_safety (accesed Septemebr 2025)