Fire in a Steam-Methane Reformer reactor of a refinery
The accident happened in a refinery unit, constructed ten years before. A pigtail ruptured in a steam reformer for the production of hydrogen, and caused a major fire, which destroyed most of the tubes (54) in one quadrant of the large steam-methane reformer furnace. No personnel was hurt. Main causes were bad weld quality and shortening of pigtails over the life of the plant, which significantly increased the cyclic stress at the root of the weld from thermal expansion and tube bowing. After the failure of the pigtail, the downstream hydrogen flew back into the reformer and ignited together with the hydrocarbons present there. Changes done in design and operating procedures are described in the article mentioned among the references.
Event Initiating System
Classification of the Physical Effects
Nature of the Consequences
Cause Comments
The INITIATING CAUSE was the failure of aged pigtails at the root of the weld, due to thermal expansion and tube bowing. Main technical causes were bad weld quality and shortening of pigtails over the life of the plant, which significantly increased the cyclic stress at the root of the weld from thermal expansion and tube bowing. After the failure of one pigtail, the downstream hydrogen flew back into the reformer and ignited together with the hydrocarbons present there. Together with the original fire from one ruptured tube, this additional massive quantity of flammable material contributed to the escalation, with the rupture of the other tubes. A shortcoming was also found in the shut-down procedure. It was optimised to protect the catalysts during transient, but it resulted far too slow such a tube rupture. The ROOT CAUSE could be attributed to shortcoming in design and manufacturing.