Fire in a refinery
The incident occurred at a hydrocracking unit, which had been shut down for maintenance. A fire occurred at a flange during the pressure tests before start-up. The fire resulted from ignition of high - pressure hydrogen-rich gas escaping from two shell-to-shell nozzle flanges on the hydrocracker reactor charge - effluent heat exchangers. Four workers had been sent to tighten flanges, which had been found leaking and had caused a partial depressurisation of the system. By the time they had assumed position, the pressure had dropped from 1600 psig to 1050 psig (respectively 110 bar and 72 bar). At the instant the hammer wrench was struck for the second time the ignition of the leaking gas occurred followed at both flanges, followed by a flash fire and a continuous flame. The unit was then depressurised via the relief system and the fire was extinguished after burning for approximately 45 minutes. Unit damage was confirmed to the insulation.
Event Initiating System
Classification of the Physical Effects
Nature of the Consequences
Causes
Cause Comments
Probable causes of ignition were: 1. Spark caused by striking the hammer wrench 2. Static build-up from the escaping hydrogen 3. Auto ignition of hydrogen due to expansion heating 4. Auto ignition of iron sulphide scale. The workers should have never bee sent at the palce of the leak without preventing search for a possible explosive gas (mixture) by gas detecting devices and strict safe procedures.