Fire in a refinery (161)

This data is from the European Hydrogen Incidents and Accidents database HIAD 2.1, European Commission, Joint Research Centre.

Fire in a refinery

The event occurred at the in the distillate hydrotreater unit of a refinery. This unit was using hydrogen to remove sulphur from a hydrocarbon feedstock. A 12-inch overhead pipe ruptured with a loud report and began releasing flammable gaseous hydrocarbons at a temperature high enough to cause spontaneous ignition. The pipe normally operates at a pressure of approximately 600 pounds per square inch (approximately 40 bar). No personnel were present in the unit when the pipe rupture occurred. The local fire brigade extinguished the ensuing fire two hours later. No employees or emergency responders were injured. Air monitoring at the perimeter of the refinery did not detect elevated concentrations of any hazardous chemicals. The fire damage was confined to other equipment in an area of to an approximately 10 square meter. Two fan-type heat exchangers were destroyed by the fire along with an approximately 50-foot section of piping; electrical conduit was also damaged by radiant heat. No blast damage was observed.
Event Date
May 20, 2006
Record Quality Indicator
Classification of the Physical Effects
Nature of the Consequences
Cause Comments

The cause of the pipe rupture could not be determined. Nevertheless, the investigation noted there have been a number of past instances of corrosion-related failures in refinery hydrotreater units.

Facility Information
Application Type
Application
hydrotreater
Specific Application Supply Chain Stage
Components Involved

gas recycle line

Storage/Process Medium
Actual Pressure
4
Location Type
Operational Condition
Pre-event Summary

the investigation reported that there have been a number of past instances of corrosion-related failures in refinery hydrotreater units.

Consequences
Number of Injured Persons
0
Number of Fatalities
0
Environmental Damage
0
Post-event Summary

The fire damage was confined to other equipment in an area of to an approximately 10 square meter. Two fan-type heat exchangers were destroyed by the fire along with an approximately 50-foot section of piping; electrical conduit was also damaged by radiant heat. No blast damage was observed. Air monitoring at the perimeter of the refinery did not detect elevated concentrations of any hazardous chemicals.

Lessons Learned
In general, it is important to carefully guarantee the integrity of piping that contains hazardous substances through rigorous inspection and testing, and to adapt them with increasing ageing of the components.
Event Nature
Emergency Action
The local fire brigade extinguished the ensuing fire two hours later. No employees or emergency responders were injured. Air monitoring at the perimeter of the refinery did not detect elevated concentrations of any hazardous chemicals.