European Hydrogen Incidents and Accidents database HIAD 2.1, European Commission, Joint Research Centre
Fire on a hydrogen compressor in a refinery (254)
This data is from the European Hydrogen Incidents and Accidents database HIAD 2.1, European Commission, Joint Research Centre.
Fire on a hydrogen compressor in a refinery
The incident occurred at a refinery unit for the desulphurisation of a light heavy oil. This unit was equipped with three hydrogen compressors. Two of them were usually operated and the third was kept in standby. On the day of the accident, one of the two operating compressors started malfunctioning. Therefore, it was decided to switch to the standby compressor. The pre-start-up inspection of this compressor did not reveal any problem. However, at the start-up of the compressor C, its recycling buffer burst, releasing hydrogen which caught fire. The rupture occurred at normal operating conditions (66 barg, 66 ° C, in presence of hydrogen sulphide). The buffer, which had the function of damper, had experienced a humid hydrogen sulphide gas environment for many years. The accident occurred due to stress corrosion cracking caused by the hydrogen sulphide gas.
The INITIATING CAUSE was loss of confinement due to corrosion. The ROOT CAUSE was due to inadequacies in material selection, design, and maintenance inspection of the failed component.