Fire on a hydrogen compressor in a refinery (254)

This data is from the European Hydrogen Incidents and Accidents database HIAD 2.1, European Commission, Joint Research Centre.

Fire on a hydrogen compressor in a refinery

The incident occurred at a refinery unit for the desulphurisation of a light heavy oil. This unit was equipped with three hydrogen compressors. Two of them were usually operated and the third was kept in standby. On the day of the accident, one of the two operating compressors started malfunctioning. Therefore, it was decided to switch to the standby compressor. The pre-start-up inspection of this compressor did not reveal any problem. However, at the start-up of the compressor C, its recycling buffer burst, releasing hydrogen which caught fire. The rupture occurred at normal operating conditions (66 barg, 66 ° C, in presence of hydrogen sulphide). The buffer, which had the function of damper, had experienced a humid hydrogen sulphide gas environment for many years. The accident occurred due to stress corrosion cracking caused by the hydrogen sulphide gas.
Event Date
January 28, 1994
Record Quality Indicator
Region / Country
Event Initiating System
Classification of the Physical Effects
Nature of the Consequences
Cause Comments
The INITIATING CAUSE was loss of confinement due to corrosion. The ROOT CAUSE was due to inadequacies in material selection, design, and maintenance inspection of the failed component.
Facility Information
Application Type
Application
Hydrodesulphurisation process
Specific Application Supply Chain Stage
Components Involved
Hydrogen compressor, damper
Storage/Process Medium
Actual Pressure
6
Design Pressure
6
Location Type
Location description
DESCRIPTION OF THE PROCESS The makeup side of the hydrogen suppy delivered 8900 std m3/h 15 bar at ambient tempearture. At the compressor, the process gas was brought from 69 bar (64 C) to 82 bar (80 C), with a flow of ca. 52,000 std m3/h.
Operational Condition
Pre-event Summary
The desulphurisation unit was equipped with 3 hydrogen recycling compressors. Two of them were usually operated and the third was kept in standby. On the day of the accident, one of the two operating compressors started malfunctioning. Therefore, it was decided to switch to the standby compressor. The pre-start-up inspection of this compressor did not reveal any problem.
Consequences
Number of Injured Persons
2
Number of Fatalities
0
Environmental Damage
69000000
Post-event Summary

Flying debris was scattered within a radius of 29 m. Total damage to the slate roof of a high-pressure gas compressor house. Damage to the hydrogen compressor, to the steel floor gratings, and to the wall of a shed.

Lessons Learned

An improved component/system design should take into account the chemical environment when in use. The following improvements should be considered: 1. For this type of components, corrosion prevention measures are required, principally by design, by using better fit-for-purpose materials. 2. The mitigation of the effect of stress corrosion on the integrity of components could be achieved by measure preventing excessive mechanical/chemical stress transients, such as using shock absorbers. 3. The inspections should be improved, by developing effective methods to monitor ageing of components under complex boundary operative conditions. Detecting incremental damage at microstructural level is a difficult task, nevertheless critical to assess component integrity.

Event Nature
Emergency Action
The unit was depressurised and the fire extinguished after 1h, due to hydrogen depletion.
Release Type
Release Substance
H2, hydrocarbons, H2 sulphide
Hydrogen Release Concentration (%)
0.00
Ignition Source
Detonation
No
Deflagration
No
High Pressure Explosion
No
High Voltage Explosion
No
References
References

JST Failure Knowledge Database: https://www. shippai. org/fkd/include/fkd_showCase. php?id=CC0000153&text1=1994-01-28 (accessed December 2024)

Event description in the French database ARIA https://www. aria. developpement-durable. gouv. fr/accident/23174/ (accessed October 2020)

Picture from the JST Failure Knowledge Database report CC0000153 (google transations)