Fire from a hydro-desulphurisation unit of a refinery
In a refinery, a fire occurred at a new reactor for the vacuum distillate hydro-desulphurisation unit. Process gas (hydrogen, hydrocarbon, etc. ) blew from a flange of upper piping in the reactor. It ignited producing 0. 5-2 meters high flames. The reason for the leak was a lack of tightness of the flange. Emergency stop of th plant was executed, thereactor was cooled and purged with nitrogen. The fire department was alarmed.
Event Initiating System
Classification of the Physical Effects
Nature of the Consequences
Causes
Cause Comments
The INITIATING CAUSE was considered a loose high-pressure flange due to uneven tightening force, on uneven thermal expansion of materials at a temperature of 390 °C. The tightening operation of hot bolting at start-up three months before was inadequate. The ROOT CAUSE was a shortcoming in the procedure for hot-bolting, tohether with a lack of effective regular inspection. There was also a alck of management actions, becasue the difficulty of hot-bolting was known and several otehr plants were able to prevent occurrence of these events.