Fire in a fertilisers plant
A gas leakage (approximately 70% hydrogen, 21% nitrogen and the rest carbon monoxide and other impurities) occurred at the connection between a temperature measurement casing and a flange in the carbonization workshop cleaning tower. The leakage was reported to the plant leader, who issued the request to the workers to use iron cards and rubber plates to plug the leak. The operation failed and the leakage continued. At 17:00, at the request of the plant leader, the workers used a tire inner tube to wrap the leak. However, due to the high pressures in the tower the high-speed by which the gas was released, and the fact that that the rubber is an electrical isolator, electrostatic sparks were produced, which ignited the gas and started a fire.
Event Date
March 13, 1995
Record Quality Indicator
Region / Country
Event Initiating System
Classification of the Physical Effects
Nature of the Consequences
Cause Comments
The direct cause of this accident was the production of sparks when attempting to stop the leak. The cause of the leak is unknown. The indirect causes of the accident were, (i) the plant operator violated rules and regulations, issuing requests disregarding health and safety; (ii) the worker also did not take effective safety measures; (iii) a lack of emergency procedures, and probably a lack of risk assessment.