Fire from cylinders when delivered
The incident occurred while delivering seven compressed hydrogen cylinders to a customer site. The store employee had already removed four cylinders from the delivery truck and carried them upright about 2 meters away. When he let them go, a "bang" sound was heard near the valve and the containers burst into flames, injuring the employee. The containers continued to burn until the gas was completely released.
Event Date
April 18, 1967
Record Quality Indicator
Event Initiating System
Classification of the Physical Effects
Nature of the Consequences
Causes

The INITIATING CAUSE was the sudden failure of (one of the) valves mounted on CGH2 cylinders. According to the KHK report, the ROOT CAUSE was an inspection failure. It would be possible also to attribute a component to (i) the design of the unloading procedure (shortcoming in safety procedures), which did not show to have any measure to protect operator, and to (ii) the design, which should prevent damage to valves and components by design.