Explosion from a venting valve (531)

This data is from the European Hydrogen Incidents and Accidents database HIAD 2.1, European Commission, Joint Research Centre.

Explosion from a venting valve

Hydrogen escaped when a venting valve was opened for the inspection of a cap. The escaped hydrogen caught fire, resulting in the death of 4 people, injuries to others 3 and damages to the plant.
Event Date
July 27, 1984
Record Quality Indicator
Region / Country
Event Initiating System
Classification of the Physical Effects
Nature of the Consequences
Causes
Cause Comments
The INITIATING CAUSE was the release and ignition of hydrogen when a tank was opened for inspection. The tank under renovation probably had not been completely degasified, hinting at a ROOT CAUSE related to inadequate procedures.
Facility Information
Application Type
Application
stationary GH2 storage
Specific Application Supply Chain Stage
Components Involved

CGH2 tank

Storage/Process Medium
Location Type
Operational Condition
Pre-event Summary
a venting valve in the tank was opened for the inspection of a cap.
Consequences
Number of Injured Persons
3
Number of Fatalities
4
Post-event Summary

The result of the fire was 4 fatalities, 3 injuries and damages to the plant.

Lessons Learned
Incidents with pressurised flammable gas systems are often caused by an inadequate purging or inertisation, with consequent flammable gas residual left inside. Any operation on tanks having previously contained any kind of flammable liquid or gas shall be performed only after a complete degasification, the results of which have to be verified my measures.
Event Nature
Release Type
Release Substance
H2 100%
Hydrogen Release Concentration (%)
0.00
Ignition Source
Detonation
No
Deflagration
No
High Pressure Explosion
No
High Voltage Explosion
No
References
References

Event nr 8761 of teh ICHEME/MHIDAS databse