Explosion at a vent stack (318)

This data is from the European Hydrogen Incidents and Accidents database HIAD 2.1, European Commission, Joint Research Centre.

Explosion at a vent stack

The incident occurred at end of a hydrogen fuel pump test, when large volume of gaseous hydrogen was vented off. An explosion occurred at or near the top of the vent stack, with damage to stack segment, vent systems, ducting, and valves. The top section of vent stack was missing (it consisted in a covering "hat" section,15 ft. length, on top of the vent stack and was housing a double reversing turning vane assembly). [Ordin, NASA (1974)]

Record Quality Indicator
Event Initiating System
Classification of the Physical Effects
Nature of the Consequences
Cause Comments

The INITATING CAUSE was the formation and ignition of an explosive air-hydrogen mixture at the end of the venting stack, where a new ''hat" section of the vent stack had been installed. Failures of internal structures had been observed prior to this incident. Therefore, the vent system had a slightly higher than normal catch tank pressures due to partial restriction of the vent stack outlet. Ignition was by static electricity or burning gas in vicinity of stack outlet. The ROOT CAUSE could be identified in an inadequate design (and possibly manufacturing) of the stack ‘hat’.

Facility Information
Application Type
Application
Aerospace
Specific Application Supply Chain Stage
Components Involved

LH2 pump, vent stack

Storage/Process Medium
Location Type
Operational Condition
Consequences
Number of Injured Persons
0
Number of Fatalities
0
Environmental Damage
0
Property Loss (offsite)

0

Post-event Summary

Losses probably limited to the vent end.

Lessons Learned

This and similar events occurred when knowledge of hydrogen fluid-dynamic and ignition behaviour was still in its infancy. The NASA was learning-by-doing from these mishaps, which were causing only some property damage. In the specific case of this event, it could be further considered if the vent ‘hat’ caused an overpressure due to some failed internal element, or just because of its geometry, forcing the vented hydrogen to reverse the flow direction. We do not know, unfortunately, the reason for the need to change the direction of the venting. It could have been the need to ensure better protections for neighbouring components.

Event Nature
Release Type
Release Substance
H2 100%
Hydrogen Release Concentration (%)
0.00
Ignition Source
References
References

Mishap no 30 in P. L. Ordin, Review of hydrogen accidents and incidents in NASA operations, 1974, NASA TM X-71565 https://ntrs. nasa. gov/citations/19740020344

Lowesmith et al. , Safety issues of the liquefaction, storage and transportation of liquid hydrogen: An analysis of incidents and HAZIDS, Int. J. Hydrogen energy (2014) https://doi. org/10. 1016/j. ijhydene. 2014. 08. 002

Hankinson and Lowesmith, Qualitative Risk Assessment of Hydrogen Liquefaction, Storage and Transportation, FCH JU project IDEALHY, Deliverable 3. 10 (2013) confidential (accessed October 2025)

Hankinson and Lowesmith, HAZIDs for Hydrogen Liquefaction, Storage and Transportation , FCH JU project IDEALHY, Deliverable 3. 11 (2013) https://www. idealhy. eu/uploads/documents/IDEALHY_D3-10%20HAZIDs_Liquefaction_Storage_Transportation_Summary_web. pdf (Only summary publicly available, accessed October 2025)