Explosion at a vent stack
The incident occurred at end of a hydrogen fuel pump test, when large volume of gaseous hydrogen was vented off. An explosion occurred at or near the top of the vent stack, with damage to stack segment, vent systems, ducting, and valves. The top section of vent stack was missing (it consisted in a covering "hat" section,15 ft. length, on top of the vent stack and was housing a double reversing turning vane assembly). [Ordin, NASA (1974)]
Record Quality Indicator
Event Initiating System
Classification of the Physical Effects
Nature of the Consequences

The INITATING CAUSE was the formation and ignition of an explosive air-hydrogen mixture at the end of the venting stack, where a new ''hat" section of the vent stack had been installed. Failures of internal structures had been observed prior to this incident. Therefore, the vent system had a slightly higher than normal catch tank pressures due to partial restriction of the vent stack outlet. Ignition was by static electricity or burning gas in vicinity of stack outlet. The ROOT CAUSE could be identified in an inadequate design (and possibly manufacturing) of the stack ‘hat’.