Explosion in a vent line
After cooldown of a LH2 system, the operator noticed cold gas issuing from a small hole in a flexible section of the vent line. Subsequent examination revealed that a deflagration had taken place in the vent line and there was a small hole in the flexible section. The vent cap showed signs of fire and was stuck in the open position. [Ordin, NASA (1974)]
Record Quality Indicator
Event Initiating System
Classification of the Physical Effects
Nature of the Consequences
Causes

The INITIATING CAUSE was the formation of hydrogen-air mixture in the vent. The mixture may have formed when the line warmed and sucked air back into the line around the seal of the vent cap or the cap may have stuck open and air diffused into the line. No source of ignition was determined. The ROOT CAUSE is unknown.