Explosion of a storage vessel in a hydrogen production facility
This incident occurred at the hydrogen production and storage unit of (probably) a power plant using hydrogen as a coolant of the turbine-generator system. Hydrogen was produced probably by water electrolysis (the source does not say it) and stored in 6 steel tanks. One of the six hydrogen storage tanks exploded killing a staff member. The investigation determined that a mixing of hydrogen and oxygen occurred in the tank. The needle valve of the hydrogen and oxygen pressure regulator as jammed, and the oxygen leaked into the hydrogen main supply line and entered the hydrogen tank. The explosion was evaluated to be equivalent to a TNT explosion in the range of 64-125 kg of TNT. The tank which exploded was pulled off from its position ripped open and completely destroyed, two other vessels fell due to the pressure wave caused by the explosion, and the other 3 were damaged in different degrees.
Event Date
September 8, 1989
Record Quality Indicator
Region / Country
Event Initiating System
Classification of the Physical Effects
Nature of the Consequences
Cause Comments
The INITATING CAUSE was a defective valve which jammed and allowed oxygen to access the hydrogen gas stream. The cause of the ignition was very possibly a spark generated by the friction of the high-speed gas flow, which can reach 100m/s when opening the valve of the vessel, driven by a pressure difference of about 392kPa. Since the needle valve had already jammed twice before, one component of the ROOT CAUSE could be related to lack of timely repair process. Also, the required diagnostic system was not in place. Apparently, there was only a hydrogen purity measurement at the generator, and not on the line to the tanks. This system, foreseen by the "Chemical Operation Management System", would avoid escalation.