Explosion of a storage vessel in a hydrogen production facility (1053)

This data is from the European Hydrogen Incidents and Accidents database HIAD 2.1, European Commission, Joint Research Centre.

Explosion of a storage vessel in a hydrogen production facility

This incident occurred at the hydrogen production and storage unit of (probably) a power plant using hydrogen as a coolant of the turbine-generator system. Hydrogen was produced probably by water electrolysis (the source does not say it) and stored in 6 steel tanks. One of the six hydrogen storage tanks exploded killing a staff member. The investigation determined that a mixing of hydrogen and oxygen occurred in the tank. The needle valve of the hydrogen and oxygen pressure regulator as jammed, and the oxygen leaked into the hydrogen main supply line and entered the hydrogen tank. The explosion was evaluated to be equivalent to a TNT explosion in the range of 64-125 kg of TNT. The tank which exploded was pulled off from its position ripped open and completely destroyed, two other vessels fell due to the pressure wave caused by the explosion, and the other 3 were damaged in different degrees.
Event Date
September 8, 1989
Record Quality Indicator
Event Initiating System
Classification of the Physical Effects
Nature of the Consequences
Cause Comments
The INITATING CAUSE was a defective valve which jammed and allowed oxygen to access the hydrogen gas stream. The cause of the ignition was very possibly a spark generated by the friction of the high-speed gas flow, which can reach 100m/s when opening the valve of the vessel, driven by a pressure difference of about 392kPa. Since the needle valve had already jammed twice before, one component of the ROOT CAUSE could be related to lack of timely repair process. Also, the required diagnostic system was not in place. Apparently, there was only a hydrogen purity measurement at the generator, and not on the line to the tanks. This system, foreseen by the "Chemical Operation Management System", would avoid escalation.
Facility Information
Application Type
Application
unspecified type of power plant
Specific Application Supply Chain Stage
Components Involved
hydrogen tank, hydrogen supply line, pressure regulator
Storage/Process Medium
Location Type
Location description
DESCRIPTION OF THE COMPONENT The stainless steel vessels had a volume of 10m3, (inner diameter: 1500mm, height 6400mm, wall thickness 12mm), Design pressure= 981kPa (9. 8 bar), working pressure is 588kPa (5. 9 bar). At the moment of the incident, the tanks were not completely filled: the exploded tank No. 1 tank was at 490kPa (4. 9 bar).
Operational Condition
Pre-event Summary
Operation practice proved that the needle valve with the function and structure adopted in this installation is very prone to jamming. The investigation revealed that it had already jammed twice before, on August 26, and again on August 31. The investigation mentions also that a 'repair' had occurred before the incident, but it does not further explain.
Consequences
Number of Injured Persons
0
Number of Fatalities
1
Lessons Learned
The investigation formulated the following recommendations: 1. When rebuilding the hydrogen production unit, a new type of pressure regulator shall be used, with a liquid level limit interlock protection device. 2. A hydrogen purity meter or an oxygen meter shall be installed on the hydrogen side to continuously monitor the hydrogen purity. 3. The management of equipment (monitoring, defect repair, replacement) shall be improved/strengthen. An immediately stop the operations shall be triggered to eliminate defects affecting hydrogen purity. 4. The equipment belonging to the hydrogen production unit shall be maintained once a year and overhauled every three years. 5. According to the requirements of "Fire Inspection Manual" and "Code for Design of Power Installations in Explosion and Fire Hazardous Environments", anti-static measures shall be in place. 6. Technical training and awareness shall be strengthen.
Event Nature
Emergency Action
The fire brigade rushed to the scene in time to extinguish the burning hydrogen storage tank and took isolation measures to prevent the accident from spreading and expanding.
Release Type
Release Substance
H2, O2
Hydrogen Release Concentration (%)
0.00
Ignition Source
Detonation
No
Deflagration
No
High Pressure Explosion
No
High Voltage Explosion
No
References
References

Zhao Yun, Cause Analysis of Hydrogen Storage Tank Explosion Accident, East China Electric Power, No. 11 (1990) 1994-2022 China Academic Journal, ElectronicPublishing House. All right reserved. www. cnki. net

Google translation

B. Wang et al. , Hydrogen related accidents and lesson learned from events reported in the in east continental Asia,#2023, ICHS-2023