Skip to main content

Explosion in a steel factory (217)

This data is from the European Hydrogen Incidents and Accidents database HIAD 2.1, European Commission, Joint Research Centre.

Explosion in a steel factory

Workers were performing demolition on a disused furnace. While removing a 10 inch valve from a pipe used to supply coke gas fuel to the furnace, flammable liquid was unexpectedly released and ignited. The flammable material consisted of methane, hydrogen, carbon monoxide and solid coke. The workers were not aware that there might be flammable material still in the pipe. The blast occurred when gas from the line came into contact with heaters which have open flames to keep nearby equipment from freezing. The accident resulted in the death of two workers and 5 others were injured. The two workers that died were working on a platform about 20 feet above the ground and did not have means to escape the fire.
Event Date
February 2, 2001
Record Quality Indicator
Classification of the Physical Effects
Nature of the Consequences
Cause Comments
The INITIATING CAUSE of the fire was the gas from the line came into contact with flames to keep nearby equipment from freezing. Root CAUSE is the inadequacy of the management systems for the supervision, planning, and execution of maintenance work. A contributing CAUSE was the absence of a program to identify and address hazards during decommissioning and demolition operations (The workers were not aware of the possible presence of flammable material still in the pipe.
Facility Information
Application Type
Application
Steel manufacturing
Specific Application Supply Chain Stage
Components Involved
furnace, heater
Storage/Process Medium
Location Type
Operational Condition
Pre-event Summary
Workers were performing demolition on a disused furnace. Heaters with open flame were used. While removing a 25 cm diameter valve from a pipe used to supply coke gas fuel to the furnace, flammable liquid was unexpectedly released and ignited.
Consequences
Number of Injured Persons
5
Number of Fatalities
2
Event Nature
Emergency Action
Responding to the accident were emergency crews (fire and ambulance) from the town of Burns Harbour and the Division's internal plant protection forces
Release Type
Release Substance
H2 11%, CH4 48%, CO 14%, CO2 7%
Hydrogen Release Concentration (%)
0.00
Detonation
No
Deflagration
No
High Pressure Explosion
No
High Voltage Explosion
No
References
References

CSB investigation, available (accessed 2July 2020) at https://www. csb. gov/bethlehem-steel-corporation-gas-condensate-fire/

From public part of MARS database