Skip to main content

Explosion at a rubber factory, caused by accidental hydrolysis of chemicals. (781)

This data is from the European Hydrogen Incidents and Accidents database HIAD 2.1, European Commission, Joint Research Centre.

Explosion at a rubber factory, caused by accidental hydrolysis of chemicals.

At a rubber factory, an explosion occurred inside a lubricant container filled with 18 tonnes of tri-(nonylphenyl) phosphate (TNPP or TNPA). This tank was typically stirred and maintained at 45°C. However, the heating circuit routed to the container had broken down 7 days earlier. With the polluted TNPP scheduled for disposal, the accident occurred during a sawing operation to remove the walkway interfering with the manhole opening. The TNPP substance underwent hydrolysis in contact with water leaking via the broken coil; the resultant phosphoric acid corroding the steel on the container caused hydrogen to form. The relatively slow hydrolysis reaction was no doubt catalysed by metal particles (rust, etc. ). A technician was seriously injured due to a fall.
Event Date
August 10, 1999
Record Quality Indicator
Region / Country
Event Initiating System
Classification of the Physical Effects
Nature of the Consequences
Cause Comments
INITIATING cause: the release of TNPP substance which underwent hydrolysis in contact with water leaking via the broken coil with consequent formation of hydrogen. Ignition very probably was catalysed by metal particles (rust, etc. ).
Facility Information
Application Type
Application
rubbers production
Specific Application Supply Chain Stage
Components Involved
a lubricant container filled with tri-(nonylphenyl) phosphite (TNPP or TNPA)
Location Type
Operational Condition
Pre-event Summary
This tank was typically stirred and maintained at 45°C; however, the heating circuit routed to the container had broken down 7 days earlier. The accident occurred during a sawing operation to remove the walkway interfering with the manhole opening. The sawing operation was aiming at disposing polluted TNPP.
Consequences
Number of Injured Persons
1
Number of Fatalities
0
Post-event Summary

A technician was seriously injured due to a fall.

Event Nature
Emergency Evaluation
A heating belt (with Tmax T° of TNPP degradation) replaced the coil, and a posted instruction reminded workers of the product's sensitivity to water.
Release Type
Release Substance
H2, H3PO4, tri-(nonylphenyl) phosphate
Hydrogen Release Concentration (%)
0.00
Ignition Source
Detonation
No
Deflagration
No
High Pressure Explosion
No
High Voltage Explosion
No
References
References

ARIA data base event no. 16467