Skip to main content

Explosion in a pharmaceutical plant (664)

This data is from the European Hydrogen Incidents and Accidents database HIAD 2.1, European Commission, Joint Research Centre.

Explosion in a pharmaceutical plant

A hydrogen gas holder exploded. It is assumed that there was diaphragm leak in the hydrogen-oxygen electrolytic cell used to produce high purity hydrogen for a pharmaceutical hydrogenation.
Event Date
January 8, 1968
Record Quality Indicator
Event Initiating System
Classification of the Physical Effects
Nature of the Consequences
Cause Comments
The INITIATING CAUSE was a through the diaphragm of the electrolyser cell membrane, which caused injection of oxygen into the hydrogen stream flow, ending in the hydrogen storage. The ROOT CAUSE is not reported, but it could be assigned to design (lack of measures of process parameters) and management (inadequate risk assessment).
Facility Information
Application Type
Application
Water electrolysis
Specific Application Supply Chain Stage
Components Involved
electrolytic cell, diafragm, gasholder
Location Type
Operational Condition
Consequences
Number of Injured Persons
0
Number of Fatalities
0
Lessons Learned
The incident occurred at the hydrogen storage tank, but it was caused by a cross-over of oxygen into the hydrogen stream flow. This incident occurred a lot of time before the incident reported in HIAD_970, occurred in Korea in 2019. Oxygen and hydrogen cross-over in the electrolytic cell is a well-known phenomenon. The severity of the occurrence depends on the electrolysis technology and the operative parameter, nevertheless it is a hazard which must be monitored, and its consequences prevented. Without proper diagnostic able to detect timely the formation of flammable mixture in the hydrogen line, this is not possible. Little is known about this incident, but an automatic system able to stop hydrogen production when concentrations trespass a threshold would have been able to avoid the creation of flammable mixture in the gas holder.
Event Nature
Release Type
Release Substance
H2 100%
Hydrogen Release Concentration (%)
0.00
Ignition Source
Detonation
No
Deflagration
No
High Pressure Explosion
No
High Voltage Explosion
No
References
References

Event in the database H2TOOLS https://h2tools. org/lessons/hydrogen-tube-trailer-burst-disc-ruptures-prematurely-while-filling (accessed Dec 2024)

primary source was in Loss Prevention, Vol 3.