Skip to main content

Explosion of a hydrogen tank (710)

This data is from the European Hydrogen Incidents and Accidents database HIAD 2.1, European Commission, Joint Research Centre.

Explosion of a hydrogen tank

A tank "filled with low-pressure hydrogen" exploded at a food manufacturing plant, killing three workers. The accident occurred when the workers were welding inside the tank after clearing hydrogen to install a hydrogen measuring device. The tank, seven metres high and two and half metres wide, was destroyed by the explosion. Police investigated the exact cause of the accident and suspected the sparks from the welding work caused the explosion with the remaining hydrogen inside the tank as the employees failed to completely remove the hydrogen before conducting the work.
Event Date
April 22, 2004
Record Quality Indicator
Event Initiating System
Classification of the Physical Effects
Nature of the Consequences
Cause Comments
Police investigated the exact cause of the accident and suspected the sparks from the welding work caused the explosion with the remaining hydrogen inside the tank as the employees failed to completely remove the hydrogen before conducting the work.
Facility Information
Application Type
Application
Food starch manufacturer
Specific Application Supply Chain Stage
Components Involved
Low -pressure hydrogen tank
Storage/Process Medium
Location Type
Location description
DESCRIPTION OF THE FACILITY The hydrogen tank was reported usually to contain 50 tonnes of hydrogen, used to make sorbitol, an artificial sweetener. The company produces starch, glucose, high fructose corn syrup, corn meal, oligosaccharide, and sorbitol.
Operational Condition
Consequences
Number of Injured Persons
0
Number of Fatalities
3
Post-event Summary

The tank "filled with low-pressure hydrogen" exploded at a food manufacturing plant, killing three workers. The tank, seven metres high and two and half metres wide, was destroyed by the explosion.

Lessons Learned
An operational procedure should ensure that the tank is completely empty of hydrogen before welding. How this can be done in practice, depends on the tank and system configuration. One of the measures could be effective purging with nitrogen, a second one suing detectors to assesses residual presence of hydrogen, In any case, all the measures must be validated according to good engineering practices before being adopted.
Event Nature
Release Type
Release Substance
H2 100%
Hydrogen Release Concentration (%)
0.00
Ignition Source
Detonation
No
Deflagration
No
High Pressure Explosion
No
High Voltage Explosion
No
References
References

Original HIAD reporting back in 2006, which does not mention the primary source